How Do You Read a York YD, YT, YS or YR Model Number and Find the Style?

On York YD, YT and YS chillers, the style (York calls it the design level or Mod) is the single letter right after the motor code, near the end of the model number. On a York YR screw chiller, it is the letter after the two-digit motor voltage code. For example, York form 160.69-RP2 shows "YD XH XD J2 - DA A" (YD, Mod A), form 160.80-RP1 shows "YS BB BA S1 – CF E S" (YS, Style E), and form 160.81-RP4 shows "YR TB TB T0 — 17 C S" (YR, Style C).

How is a York YD model number laid out?

York form 160.69-O2 (YD Mod A and B operation and maintenance), page 4, and the YD renewal-parts forms list these fields, left to right:

Field Example "YD XH XD J2 - DA A" Codes listed by York
Model YD YD
Evaporator code XH XF, XH, YF, YG, YH, ZF, ZG, AF, AG, AH (160.69-O2)
Condenser code XD XA, XB, XC, XD, YA, YB, YC, YD, ZA, ZB, ZC, ZD, AA, AB, AC, AD (160.69-O2)
Compressor code J2 J1, J2, J3, J4, J5 (160.69-O2); K1, K2, K3, K4, K7 (160.69-RP3, Mod C)
Power supply - "-" for 60 Hz, "5" for 50 Hz
Motor code DA Each 60 Hz code has a 50 Hz partner that starts with 5 (for example CW/5CS, DA/5DA, DL/5DL)
Design level (Mod) A A, B or C (160.69-O2)

Form 160.69-RP3 (Mod C) prints "YD ND BE K2 — DA C S". Here K2 is the compressor code, DA the motor code, C the design level (Mod C), and the trailing S marks special modifications. Form 160.69-RP2 covers YD "Style A-C" and has parts tables for both J-series (J1/J2, J3/J4/J5, J7) and K-series (K1/K2, K3/K4, K7) compressors, so read the design letter itself rather than guessing the Mod from the compressor.

How do you find the style on a York YT model number?

York literature supplement 160.48-RP6 (YT Style J) prints the example "YT G3 A3 E2 5 CK J S". Reading left to right:

Field Example Codes listed
Model YT YT
Cooler code G3 G0, G1, G3, H1, H3, J1, J3, K1, K3, K4, K6, K7, K9, L1, L3, L4, L6
Condenser code A3 A1 to A4, B1 to B4, C1 to C8, D1 to D8
Compressor code E2 (not decoded in the supplement)
Power supply 5 "-" = 60 Hz, "5" = 50 Hz
Motor code CK Two-letter motor code (CK in York's example)
Design level J J
Special features S "S – Call factory for details."

So the letter after the motor code is the YT Mod: J in this example.

How do you find the style on a York YS screw chiller?

York form 160.80-RP1 (710), for "YS BA CB S0 thru YS FA FB S5" Style E, 100 to 675 tons, prints "YS BB BA S1 – CF E S". Its field labels are model code, cooler code, condenser code, compressor code, power supply ("–" = 60 Hz, "5" = 50 Hz), motor code, design level and special features. In the example the cooler is BB, the condenser BA, the compressor S1, the motor code CF and the design level E.

Why is the York YR different?

The YR twin-screw chiller puts a two-digit motor voltage code where the YD, YT and YS put a letter motor code. York form 160.81-RP4 (622), Style C, prints "YR TB TB T0 — 17 C S", and form 160.81-RP1 (622), Style A, prints "YR TB TB T0 — 17 A S". The fields are model, evaporator code, condenser code, compressor code (T0 to T3), power supply, motor voltage, modification level and special features. The letter after the voltage code is the style.

YR motor voltage code Voltage (160.81-RP4)
17 200/208-3-60
28 230/240-3-60
40 380-3-60
46 440/460/480-3-60
58 575/600-3-60
50 380/400-3-50
55 415-3-50

Both YR forms cover models "YR TA TA T0 thru YR VD VD T1, YR WA WA T2 thru YR XD XD T3", 200 to 430 tons at 60 Hz and 170 to 365 tons at 50 Hz, R-134a.

Is a "YD..." number always a YD chiller?

No. York compressor model numbers also start with YD. Form 160.75-RP2 lists YK compressors YDHK 76 (K1), YDHK 84 (K2), YDHL 95 (K3), YDHL 106 (K4) and YDHA 119 (K7). Form 160.48-RP1 covers YDTL108, YDTL120 and YDTL126, which are YT compressors. If the number you have starts with YDH or YDT, it is likely from a compressor nameplate, not the chiller nameplate.

Parts involved

Component Role Where to find it
Parts by model and style Each model page lists parts from that style's York renewal-parts manuals York YT, YS, YR & YD Legacy Chiller Parts
YT oil filter element Listed in 160.48-RP6 for YT Style J York 026-37915-000 Element, Filter (10 Micron) | OEM Chiller Part
YR oil filter kit Listed in 160.81-RP4 for YR Style C York 364-50438-000 Oil Filter Element Kit | OEM Chiller Part
Common O-ring Listed on our YD Mod A to C, YT Mod J, YS Style E and YR Style A and C pages York 028-12961-012 O-Ring, 0.364" x 0.070" | OEM Chiller Part

Which York units this applies to

Scope: York forms 160.69-O2 and 160.69-RP2 (522) for YD Style A to C, 160.69-RP3 for YD Mod C, 160.48-RP6 supplement for YT Style J, 160.80-RP1 (710) for YS Style E, and 160.81-RP1 (622) and 160.81-RP4 (622) for YR Style A and C. Code lists are as printed in those forms; other styles may use other codes. YK, YK-EP and YMC2 nomenclature is not covered here.

Before you order

Copy the full model number and serial number from the chiller nameplate, not from the compressor or starter. Send them with the part number you need. To confirm fit, contact us at help@totalhvacparts.com or 610-487-7999. For part number formats, see How to Look Up a York Part Number.

Frequently Asked Questions

Where is the Mod letter in a York YD model number?

It is the letter after the motor code. In York's example "YD XH XD J2 - DA A" from form 160.69-RP2, DA is the motor code and A is the design level, so the unit is a YD Mod A.

What does the 5 mean in a York YT model number?

It is the power supply code. York's YT, YS, YD and YR nomenclature uses "-" for 60 Hz and "5" for 50 Hz.

How do I tell a York YR Style A from a Style C?

Read the letter after the two-digit motor voltage code. York prints "YR TB TB T0 — 17 A S" for Style A (160.81-RP1) and "YR TB TB T0 — 17 C S" for Style C (160.81-RP4).

What does 46 mean in a York YR model number?

Per York form 160.81-RP4, motor voltage code 46 is 440/460/480-3-60.

Is YDHK 84 a York chiller model?

No. York form 160.75-RP2 lists YDHK 84 as a YK compressor model, compressor code K2.

Sources

Reading a nameplate is safe, but chiller panels and starters carry line voltage. Any service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.