York 028-12961 is one O-ring family, and the dash number sets the size. On a YK Style G with Q3–Q7 compressors, York form 160.75-RP1 calls for 11 of the -012 (.364 ID × .070) and 7 of the -015 (.739 ID × .070) in the unit piping alone. Other dash numbers seal the oil filter, the oil pump housing, the sight glasses, the condenser drain plug and the relief valves.
What sizes are the common 028-12961 O-rings?
Sizes below are inside diameter × thickness in inches, as printed in the York Style G (160.75-RP1) and Style H (160.76-RP1) unit components manuals.
| Dash no. | York size (ID × thk) | Where York lists it on YK Style F, G, H |
|---|---|---|
| -001 | .351 × .072 | Unit piping; oil filter arrangement (item 7); oil pump housing terminal (Style G) |
| -002 | .414 × .072 | Unit piping; evaporator and condenser pressure transducers (Style F) |
| -003 | .468 × .078 | Unit piping; oil pump housing; 3/8" tube angle stop valves (Style F) |
| -004 | .644 × .087 (Style H lists 2.20 × 16.40 mm) | Oil pump housing; temperature sensors (Style F); some variable orifice valve assemblies (Style G) |
| -006 | .924 × .116 | Unit piping; oil filter arrangement (item 8); oil pump housing; variable orifice valves |
| -008 | 1.17 × .116 | Unit piping; drain plug (condenser drain plug in Style F); oil pump housing; relief valves on some shells |
| -010 | 2.33 × .118 | Oil pump housing, P7–P9/H9 and K compressors (Style G) |
| -012 | .364 × .070 | Unit piping (the most-used size); dehydrator and solenoid valve (Style F) |
| -013 | .489 × .070 | Unit piping, including the thermal expansion valve (item 7A, Style G); oil cooler (Style F) |
| -015 | .739 × .070 | Unit piping; oil filter arrangement (item 9); oil cooler and stop valves (Style F) |
| -016 | .926 × .070 | Unit piping; oil pump housing on K compressors (Style G) |
| -017 | Not sized in the RP manuals reviewed | Evaporator and condenser relief valves and 3-way valves, by shell code |
| -021 | .301 × .064 (Style H) | Variable speed oil pump control panel |
| -035 | .487 × .103 | Oil pump housing |
| -036 | 2.090 × .118 | Sight glass |
York's own lists are not perfectly consistent. Form 160.75-RP1 gives -003 as .468 × .078 in one table and .468 × .070 in another, and gives -001 as ".351 OD" in one row. When a size matters, match the dash number, not the size. Some of our listing titles give the size in millimetres (thickness × ID) rather than inches. The dash number is what identifies the part.
How many O-rings does a YK Style G unit piping job use?
The quantities below are per chiller from 160.75-RP1, Table 2 (unit piping, Q3–Q7 compressors). They explain why a full re-seal goes through so many -012 and -015 rings.
| Dash no. | Item | Qty |
|---|---|---|
| -012 | 165 | 11 |
| -015 | 31 | 7 |
| -003 | 166 | 7 |
| -001 | 59 | 3 |
| -002 | 164 | 3 |
| -016 | 32 | 2 |
| -008 | 167 (plus 1 for the drain plug, item 169) | 2 + 1 |
| -036 | 171, sight glass | 2 |
| -006 | 27 | 1 |
| -013 | 7A and 26 | 1 each |
Quantities change with the compressor. On Q7, P7–P9 and H9 compressors (Table 5), -012 drops to 10 and -008 rises to 5. On K1–K4 and K7 compressors (Table 8), -015 rises to 11 and -016 to 7.
Which O-rings seal the YK oil filter?
Form 160.75-RP1, Table 10 (Style G) and form 160.76-RP1, Table 4 (Style H) list the same O-rings for the filter piping. The filter housing itself takes a different, larger O-ring, 028-14404-000 (3.484 ID × .139).
| Part | Single filter | Dual filters |
|---|---|---|
| 028-12961-001 (item 7) | 1 | 2 |
| 028-12961-006 (item 8) | 2 | 5 |
| 028-12961-015 (item 9) | 1 | 6 |
| 028-14404-000, filter housing (item 1B; quantities from 160.76-RP1) | 1 | 2 |
For filter change timing and the element number, see York YK Style F, G and H Oil Filter: When to Change It, and for kits, York YK Chiller PM Kits: Which Kit Fits Which Style.
Which O-rings are in the oil pump housing?
The oil pump housing tables in 160.75-RP1 (Tables 3, 6 and 9) list -001 (terminal), -003, -004, -006, -008 and -035 on every compressor group. P7–P9/H9 and K compressors add -010 (2.33 × .118). On K compressors, York lists -016 at item 20 where the Q3–Q7 table lists -008.
Parts involved
Which York units this applies to
- YK Mod G: the 160.75-RP1 tables above.
- YK Mod H: sizes and oil filter O-ring quantities from 160.76-RP1 (Table 2 unit piping counts differ slightly from Style G).
- YK Mod F: locations from 160.73-RP1, including P1–P6 and H & J builds.
- YD Mod C: our page lists many of the same dash numbers; confirm by model and serial.
- YKEP Mod A: our page lists many of the same dash numbers; confirm by model and serial.
Scope: Sizes, item numbers and quantities come from York forms 160.75-RP1 (YK Style G), 160.76-RP1 (YK Style H) and 160.73-RP1 (YK Style F). YD and YKEP chillers have their own manuals, not covered here. York marks the Style F and H RP manuals as obsolete and for reference only.
Before you order
Read the chiller model and serial number from the nameplate and name the assembly you are re-sealing. If you can, read the York number off the parts list for your style rather than measuring an old ring. To confirm the dash numbers and counts, contact us at help@totalhvacparts.com or 610-487-7999.
Frequently Asked Questions
What is York part 028-12961-012?
It is a York O-ring sized .364 ID × .070 in York form 160.75-RP1. The YK Style G unit piping table for Q3–Q7 compressors lists 11 per chiller.
Which O-ring goes on a York YK sight glass?
York lists 028-12961-036 (2.090 ID × .118) as the sight glass O-ring, 2 per chiller, in forms 160.75-RP1 and 160.73-RP1.
What O-ring does the York YK oil filter housing use?
The filter housing O-ring is 028-14404-000, listed as 3.484 ID × .139 in York forms 160.75-RP1 and 160.76-RP1. The filter piping also uses 028-12961-001, -006 and -015.
Which O-ring is on the York YK condenser drain plug?
York forms 160.75-RP1 and 160.73-RP1 list 028-12961-008 as the drain plug O-ring, 1 per chiller.
Sources
- York form 160.75-RP1, YK Style G Unit Components (Tables 2, 3, 5, 6, 8, 9, 10 and 22–24)
- York form 160.76-RP1, YK Style H Unit Components (Tables 2–4 and 10–12, O-ring sizes and oil filter quantities)
- York form 160.73-RP1, Unit Components, Model YK (Style F) (Tables 1, 3, 5, 6, 10, 11, 14, 15)
- Live product titles for the parts listed above, as shown on each product page
Opening refrigerant and oil connections on a chiller releases pressurized refrigerant and oil. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.