CH02 and CH06 on an LG Multi V indoor unit mean one of the two coil pipe temperature sensors reads open or shorted: CH02 is the inlet pipe sensor and CH06 the outlet pipe sensor. The LG MULTI V 5 Outdoor Unit Service Manual (Error Nos. 01, 02, 06 and 17, p.136) sends you to the plug, then the sensor's resistance, then the indoor PCB. Most LG pipe sensors are 5 kΩ parts such as LG EBG61325805 NTC Thermistor Assembly – Multi V and mini split system and LG EBG61287707 NTC Thermistor Assembly – Multi V and mini split system; the right one depends on its location on your model.
What do CH02 and CH06 mean?
| Code | LG description | Sensor and plug (ducted manual MFL69041302) |
|---|---|---|
| CH02 | "Indoor unit inlet pipe temperature sensor communication error." | Th2, pipe in temperature, CN-PIPE_IN (White) |
| CH06 | "Indoor unit or hydro kit outlet pipe temperature sensor error." | Th3, pipe out temperature, CN-PIPE_OUT (Red) |
The LG Multi V ducted indoor unit service manual MFL69041302 words both causes plainly: the inlet or outlet pipe sensor "of indoor unit is open or short". The LG MULTI V S Outdoor Unit Service Manual labels the same plugs CN-PIPE IN and CN-PIPE OUT on its Error 01/02/06 page.
What should an LG pipe sensor read?
The LG Multi V S service manual MFL69740704 lists the "Pipe temp sensor" at 10 kΩ at 10 °C (50 °F), 5 kΩ at 25 °C (77 °F) and 1.8 kΩ at 50 °C (122 °F). It sets the error limits at "more than 100 kΩ (open) or less than 100 Ω (short)". The MV5 manual gives the tolerance as ±5%. Fahrenheit figures are our conversions.
The pipe sensors are not the same as the 10 kΩ air sensor behind CH01, so do not judge a pipe sensor against the air-sensor curve. Match the part by location, as shown below.
How do I check CH02 or CH06?
- Identify the sensor. CH02 is CN-PIPE_IN; CH06 is CN-PIPE_OUT. Trace the lead from the plug to the coil.
- Check the plug. "Is the sensor properly connected to the PCB?" If not, "Connect to the PCB properly."
- Measure it. Unplug and measure resistance. The MV5 flowchart prints the step "Measure the resistance of outlet pipe temperature sensor." Compare with the 5 kΩ-at-25 °C curve at the actual pipe temperature.
- Bad reading: "Change the sensor."
- Good reading, code stays: "Replace the PCB." Run auto addressing after replacing an indoor PCB.
Field practice, not from the manual: measure with the sensor at a known temperature. A sensor clipped to a cold pipe in cooling will read well above 5 kΩ and is not faulty for that reason.
Which pipe sensor part number do I need?
Use the location number on your model page, not the description. On the ARNU073TUD4, LG lists the two 5 kΩ pipe sensors at locations 263230B (EBG61287706, with EBG61287707 listed as interchangeable) and 263230C (EBG61325805); 263230A is the 10 kΩ room sensor behind CH01. The full location and item-spec breakdown is in our LG indoor thermistor guide.
LG's item specs do not say which of 263230B and 263230C is the inlet and which the outlet sensor. Trace the lead from CN-PIPE_IN or CN-PIPE_OUT to its sensor, then read the location from the exploded view on your model page or the number on the old sensor. Other chassis list different numbers: EBG61325805's LG fit list includes the ducted M1A4 and M2A4 sizes and the MAA4 and TAA4 chassis, and EBG61287707's includes 4-way cassette TNA4, TMA4 and TPC4 models and the B8A4 ducted units.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Pipe thermistor, 5 kΩ (263230C on ARNU073TUD4) | Replace when the CH02 or CH06 sensor reads open, short or out of tolerance. | LG EBG61325805 NTC Thermistor Assembly – Multi V and mini split system |
| Pipe thermistor, 5 kΩ (263230B on ARNU073TUD4) | As above; LG lists EBG61287706 as interchangeable. | LG EBG61287707 NTC Thermistor Assembly – Multi V and mini split system |
| Indoor main PCB (TUD4 and TTD4 chassis) | "Replace the PCB" only after the plug and sensor test good. | LG EBR81767920 Main PCB Assembly – Multi V indoor unit |
A pipe sensor that reads correctly but sits loose on the pipe gives wrong control readings without setting CH02 or CH06. If the unit reports superheat-related trouble instead, see LG CH150 and indoor EEV checks.
Which units this applies to
- LG Multi V indoor units (ARNU and others) showing CH02 or CH06, on Multi V 5, Multi V S and other Multi V systems that use the same indoor code table.
- CH06 is also used for the hydro kit outlet pipe sensor ("Indoor unit or hydro kit outlet pipe temperature sensor error"); this article covers air-side indoor units.
Scope: Flowchart text is from the MV5 manual p.136, values from LG manual MFL69740704 and sensor names from LG manual MFL69041302. Locations, item specs and fit lists are LG's parts-by-model data as shown on our pages.
Before you order
Read the full model and serial number from the unit's nameplate, note the exact code shown (including any unit or HR-number digits), and if you can, the LG part number printed on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, code and the readings you took.
Frequently Asked Questions
What is the difference between CH02 and CH06 on an LG Multi V?
CH02 is the indoor inlet pipe sensor (CN-PIPE_IN) and CH06 the outlet pipe sensor (CN-PIPE_OUT). Both mean the sensor reads open or shorted.
What resistance should an LG indoor pipe sensor have?
LG's Multi V S manual lists 10 kΩ at 10 °C, 5 kΩ at 25 °C and 1.8 kΩ at 50 °C, with an error above 100 kΩ or below 100 Ω.
Are EBG61287707 and EBG61287706 interchangeable?
Yes. LG lists EBG61287706 as interchangeable with EBG61287707.
Is EBG61325805 the inlet or the outlet sensor?
LG's item spec does not say. On the ARNU073TUD4 it sits at location 263230C; trace the lead from CN-PIPE_IN or CN-PIPE_OUT to confirm which one failed.
Sources
- LG MULTI V 5 Outdoor Unit Service Manual (no printed form number), Error Code Tables p.126 and Error Nos. 01, 02, 06 and 17, p.136. Cited by name and page; not linked.
- LG Multi V S service manual MFL69740704, Error Nos. 01/02/06 page.
- LG Multi V ducted indoor unit service manual MFL69041302, piping diagram (Th2, Th3) and self-diagnosis table.
- LG MULTI V S Outdoor Unit Service Manual, Error Nos. 01, 02, 06 (connector labels).
- LG parts-by-model, interchange and item-spec data as shown on our LG model and product pages.
Indoor unit service involves line-voltage wiring, rotating fans and condensate near live parts. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.