On an LG Multi V indoor unit, CH01 means the indoor air temperature sensor reads open or shorted. The LG MULTI V 5 Outdoor Unit Service Manual (Error Nos. 01, 02, 06 and 17, p.136) lists three causes: the sensor, its connection on the indoor unit PCB, or a failed indoor PCB. Measure the sensor before ordering. On many ARNU chassis the room sensor is LG EBG61106804 NTC Thermistor Assembly – Multi V and mini split system, the part LG's item spec describes as "10KOHM,ROOM".
What does CH01 mean on an LG Multi V?
LG's code tables word it as "Indoor unit return air or optional remote wall temperature sensor communications error." So the code covers the air sensor in the unit's return air path, or a remote wall sensor if one is fitted. The LG Multi V ducted indoor unit service manual MFL69041302 (M1, M2 and M3 ducted chassis) gives the plain meaning: "Air temperature sensor of indoor unit is open or short". Its piping diagram names this sensor "Th1 Thermistor for room air temperature CN-ROOM (Yellow)".
The same flowchart also covers CH02 and CH06, the two pipe sensors. They use a different resistance curve; see which LG indoor thermistor is which.
What resistance should an LG indoor air sensor read?
The MV5 manual says sensor resistance "will vary with the temperature" and gives a ±5% tolerance, but its value table does not survive in the text copies we could read. The LG Multi V S service manual MFL69740704 prints the values clearly on its Error 01/02/06 page:
| Sensor (LG wording) | 10 °C (50 °F) | 25 °C (77 °F) | 50 °C (122 °F) |
|---|---|---|---|
| Air temp sensor | 20.7 kΩ | 10 kΩ | 3.4 kΩ |
| Pipe temp sensor | 10 kΩ | 5 kΩ | 1.8 kΩ |
The same page says: "In case the value is more than 100 kΩ (open) or less than 100 Ω (short), Error occurs". Fahrenheit figures in the table are our conversions; LG prints °C on this page.
How do I check CH01 step by step?
- Find the plug. The air sensor plugs into CN-ROOM on the indoor PCB (CN_ROOM(YL) on the M1/M2/M3 ducted wiring diagram). The first flowchart question is "Is the sensor properly connected to the PCB?" If not: "Connect to the PCB properly."
- Measure the sensor. Power off, unplug the sensor and measure across its two leads. Compare the reading with the table above at the actual air temperature. The flowchart asks: "Is the resistance value of the sensor normal?"
- Bad reading: "Change the sensor." An open (over 100 kΩ) or near-zero (under 100 Ω) reading is the fault the code describes.
- Good reading, code stays: "Replace the PCB." That is the indoor unit PCB, which reads the sensor.
Field practice, not from the manual: check the sensor lead along its whole run before you condemn it. A pinched or chafed lead at a panel edge reads open or short just like a failed bead.
Which part number is the room sensor?
LG lists every indoor thermistor as "Thermistor Assembly,NTC", so use the location number and LG's item spec. On the ARNU073TUD4, the part at location 263230A is EBG61106804 (it replaced the obsolete 6323A10002B), and only that one carries the "ROOM" spec. Its LG fit list also includes the ducted ARNU073 to 243 M1A4 and M2A4 (for example the ARNU123M2A4), the MAA4 and TAA4 chassis and many others. LG's data also lists:
- LG EBG61106816 NTC Thermistor Assembly – Multi V and mini split system as a one-way substitute for EBG61106804. LG says not to use EBG61106804 in place of EBG61106816. See what LG’s interchange labels mean.
- 6323A10002E as interchangeable with EBG61106804.
If your unit uses a remote wall sensor instead of the return-air sensor, the code is the same, but the part is the remote sensor. Match it from the number on the sensor itself.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Indoor air (room) thermistor, 10 kΩ | Replace when the sensor reads open, short or out of tolerance for the actual temperature. | LG EBG61106804 NTC Thermistor Assembly – Multi V and mini split system |
| LG one-way substitute | LG's listed substitute for EBG61106804 on the models in its fit list. | LG EBG61106816 NTC Thermistor Assembly – Multi V and mini split system |
| Indoor main PCB (ARNU073/093/123 TUD4, ARNU183/243 TTD4) | "Replace the PCB" when the sensor and plug test good and CH01 stays. Run auto addressing after a board change. | LG EBR81767920 Main PCB Assembly – Multi V indoor unit |
Other chassis use other indoor boards; see LG indoor main PCB vs communication PCB.
Which units this applies to
- LG Multi V indoor units (ARNU and others) that display CH01, on Multi V 5, Multi V S and other Multi V outdoor systems that use the same indoor code table.
- The resistance values come from LG's Multi V S service manual; the connector names come from LG's M1/M2/M3 ducted indoor manual.
Scope: Codes, causes and flowchart text are from the MV5 manual (Error Nos. 01, 02, 06 and 17, p.136), with resistance values from LG manual MFL69740704 and sensor names from LG manual MFL69041302. Part fits are LG's parts-by-model data on our product and model pages. A different indoor chassis may list a different number at 263230A.
Before you order
Read the full model and serial number from the unit's nameplate, note the exact code shown (including any unit or HR-number digits), and if you can, the LG part number printed on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, code and the readings you took.
Frequently Asked Questions
Is CH01 on an LG Multi V a communication fault?
No. LG's table uses the word "communications", but the error is an air temperature sensor that reads open or shorted, as LG's ducted indoor manual states.
What should an LG indoor air sensor read at 77 °F?
LG's Multi V S manual lists the air temperature sensor at 10 kΩ at 25 °C (77 °F), 20.7 kΩ at 10 °C and 3.4 kΩ at 50 °C.
When does LG say to replace the indoor PCB on CH01?
When the sensor is properly connected and its resistance is normal but the error remains. The flowchart action is "Replace the PCB."
Can I use EBG61106804 in place of EBG61106816?
No. LG lists EBG61106816 as a one-way substitute for EBG61106804, not the other way round.
Sources
- LG MULTI V 5 Outdoor Unit Service Manual (LG Electronics U.S.A., no printed form number), Error Code Tables p.126 and Error Nos. 01, 02, 06 and 17, p.136. Cited by name and page; not linked.
- LG Multi V S service manual MFL69740704, Error Nos. 01/02/06 page (resistance values, open/short limits).
- LG Multi V ducted indoor unit service manual MFL69041302, piping diagram (Th1 CN-ROOM) and self-diagnosis table.
- LG parts-by-model, interchange and item-spec data as shown on our LG model and product pages.
Indoor unit service involves line-voltage wiring, rotating fans and condensate near live parts. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.