On a Greenheck direct gas-fired make-up air unit built with the optional UV scanner, the scanner is the flame sensor, so a unit that lights and then drops out points first at the scanner, its spark generator and its amplifier card. Greenheck manual 482886 (Rev. 12) says the UV scanner "can be used in lieu of a flame rod" and that "A special spark generator and rectification amplifier card are required with the use of this option." We list the Greenheck 871565 UV Conversion Kit for flame sensing and the 459021 UV flame detector; clean the scanner and prove the spark and the burner airflow before you buy either.
How does the UV scanner work on a Greenheck direct-fired unit?
Manual 482886 covers models DGX, TSU and VSU. It describes the UV scanner in its control identification pages and mentions it again in the maintenance list:
| Topic | What 482886 says | Page |
|---|---|---|
| What it is | "The optional UV scanner is a flame sensing device that can be used in lieu of a flame rod." | 31 |
| How it senses flame | "The UV eye senses the flame by detecting the ultraviolet light produced by the flame." | 31 |
| Extra hardware | "A special spark generator and rectification amplifier card are required with the use of this option." | 31 |
| Maintenance | "Inspect and clean the flame rod or UV scanner." | 50 |
| Industrial flame safeguard | "A self-diagnostic check is performed every five seconds." | 44 |
Two things follow from that. First, a UV unit is not a flame rod unit with a different sensor bolted on. The spark generator and the amplifier card are matched to the UV option. Second, the scanner is a maintenance item: the seasonal burner checks put it next to the flame rod for inspection and cleaning.
What should you check when a UV-equipped unit loses flame?
The troubleshooting charts in 482886 (pages 53 to 57) are written around the pilot and flame sensing sequence. These are the chart's questions for the 120V industrial pilot system, in order, with our notes for a UV unit:
- Check the self-test light. The chart asks: "Does power light on the flame safeguard blink approximately every 5 seconds as it performs a self-diagnostics check?" If it does not, check the subbase wiring, and replace the flame safeguard if the fault persists.
- Record the code before you reset. If the alarm light is blinking, the chart says: "Record the flash code from the alarm light." Investigate the cause, then press reset.
- Check the test/run switch. A control left in test will not run the normal sequence. The chart's action is "Move switch to 'Run'."
- Look for the pilot. The chart asks "Pilot flame visible through sight glass?" With no pilot, it sends you to the spark. Where the spark is missing and the wiring is good, the corrective action is "Spark generator faulty. Replace spark generator." On a UV unit, the manual says the spark generator is a special one, so replace it like for like.
- Read the flame signal. The chart says: "With a flame signal of 1.25 VDC or higher, the red flame light on the flame safeguard should be illuminated." The Honeywell start-up steps (page 34) add that the signal "must be above 1.25 VDC and steady."
- Lock out, then inspect and clean the scanner. This is the maintenance step from page 50. Field practice, not from the manual: wipe the scanner lens with a clean, dry, lint-free cloth, make sure nothing blocks its view of the flame, and check the scanner cable and connector for heat damage.
- Prove burner airflow. The start-up section says proper air velocity over the burner is critical and that a unit outside specification may have sporadic shutdowns. Set the burner pressure drop to 0.625 to 0.675 in. wg for natural gas, or 0.8 to 0.9 in. wg for LP.
- Only then suspect the amplifier or flame safeguard. If the scanner is clean, the pilot is lit, the airflow is right and the signal is still low, have the amplifier card and burner control tested to the control maker's instructions.
Is there a separate flame signal value for a UV scanner?
Not in 482886. The values in the manual are given for the pilot systems, not for each sensor type:
| Pilot system (482886) | Minimum flame signal | Page |
|---|---|---|
| 120V pilot, Honeywell | Above 1.25 VDC and steady | 34 |
| 120V pilot, Baso | 1 µA DC | 35 |
| Industrial pilot chart | 1.25 VDC or higher lights the red flame light | 54 |
Read the signal at the same test points you would use on a flame rod unit. If your amplifier's own instructions give a different figure, follow the control maker's figure for that amplifier.
Can a flame rod unit be converted to UV?
The manual presents UV as an option, and we list a Greenheck kit titled for UV conversion. The manual does not give a conversion procedure or a kit contents list. It does say the UV option needs a special spark generator and a rectification amplifier card. Before converting, confirm with your unit's serial number that the kit and your burner control match.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| UV conversion kit | Greenheck kit listed for UV flame sensing; confirm contents and fit by unit serial number | Greenheck 871565 Uv Conversion Kit, Flame Sensing |
| UV flame detector | The scanner itself; replace if it is damaged or still fails after cleaning | Greenheck 459021 Uv Flame Detector, Honeywell |
| Flame signal amplifier | The manual requires a rectification amplifier card with UV; match the model printed on your card | Greenheck 459022 Flame Signal Amplifier, R7849A1023 |
| Spark generator | Chart action when the spark is missing; UV units need a special spark generator, so match your old one | Greenheck 450496 Spark Generator, Honeywell, Q624A1014/B |
| Flame safeguard | Replace only after the scanner, spark, pilot and airflow check out | Greenheck 386999 Control, Flame Safeguard, RM7897A2002/U |
For flame rod units, see our article on Greenheck direct-fired flame failure and flame rod 452942. For ignition problems, see no spark or no pilot and spark rod 452943.
Which units this applies to
- Greenheck DGX direct gas-fired make-up air units covered by document 482886 and built with the optional UV scanner.
- Greenheck TSU and VSU industrial space heat units covered by the same manual.
- Older direct-fired units built before the current manual have their own IOM. Use the manual that matches your nameplate.
Scope: The UV scanner description, the required hardware, the chart questions and actions, and the flame signal and burner pressure values come from Greenheck document 482886, Rev. 12. The manual does not name a part number for the scanner, the amplifier card or the spark generator. The listings above are matched by title only, so check the model on your old part and your unit's serial number before ordering.
Before you order
Read the unit model and serial number from the nameplate, and copy the model numbers from the scanner, the amplifier card and the spark generator. Note whether the unit is commercial or industrial, and whether it burns natural gas or LP. To confirm fit, contact us or email help@totalhvacparts.com with those numbers, or browse Valent, Innovent & Greenheck Replacement Parts.
Frequently Asked Questions
Does a Greenheck direct-fired make-up air unit use a flame rod or a UV scanner?
Either, depending on how it was built. Greenheck manual 482886 says the optional UV scanner is a flame sensing device that can be used in lieu of a flame rod, so check which one your unit has before ordering parts.
What extra parts does the UV scanner option need?
Manual 482886 says a special spark generator and rectification amplifier card are required with the UV option. Match those parts to the ones in your unit, not to a flame rod unit.
How often should the UV scanner be cleaned?
Greenheck's seasonal maintenance list in 482886 says to inspect and clean the flame rod or UV scanner. Clean it as part of seasonal maintenance and whenever the flame signal drops.
What flame signal should a Honeywell control show?
The Honeywell start-up steps in 482886 say the signal must be above 1.25 VDC and steady. The industrial pilot chart says the red flame light should be on at 1.25 VDC or higher.
Sources
- Greenheck document 482886, Direct Gas and Industrial Space Heat Make-Up Air, Installation, Operation and Maintenance Manual (Models DGX, TSU, VSU), Rev. 12, December 2025
- Live product titles for the parts listed above, as shown on each product page
Direct gas-fired make-up air units carry line voltage, high-voltage ignition and natural gas or LP. Service should be performed only by qualified personnel, following Greenheck's manual for your unit, local gas codes and your facility's lockout/tagout procedures.