When a Greenheck direct gas-fired make-up air unit lights and then drops the flame or locks out, the first thing to measure is the flame signal. Greenheck manual 482886 says the signal on a Honeywell burner control must be above 1.25 VDC and steady, and the minimum on Baso controls is 1 µA DC. The usual fixes are cleaning or replacing the flame rod (Greenheck 452942) and correcting pilot gas pressure, before anyone condemns the flame amplifier or burner control.
What flame signal should a Greenheck direct-fired burner have?
Greenheck document 482886 (Direct Gas and Industrial Space Heat Make-Up Air IOM, Rev. 12) gives a minimum for each pilot system:
| Pilot system (482886) | Minimum flame signal | Where it is measured |
|---|---|---|
| 120V pilot, Honeywell | Above 1.25 VDC and steady | Flame signal test ports (+/-) on the burner controller |
| 120V pilot, Baso | 1 µA DC; measured with the pilot lit and no main gas flowing | Baso control |
| Commercial pilot (120V, burners over 18 in.; 24V, burners 18 in. and under) | 1.0 micro amps or higher (troubleshooting chart) | Terminals FC + and - on the flame safeguard amplifier |
The manual also notes that all industrial pilot systems are 120V. Greenheck's Pilot Ignition Quick Start Guide (document 694984) repeats the 1.25 VDC figure: measure the signal with the pilot lit and the main valve closed, then again after the heat call (W1) is re-energized, when it should be above 1.25 VDC and steady.
What does Greenheck's troubleshooting chart say causes flame failure?
The direct gas-fired heat troubleshooting pages of 482886 walk through these questions. Each line below is a check in the chart and Greenheck's corrective action when the answer is wrong:
| Check (482886) | Corrective action |
|---|---|
| Flame rod dirty or corroded? | Clean flame rod. Remove corrosion with emery cloth. |
| Flame rod or flame rod porcelain cracked or deteriorated? | Replace flame rod. |
| 1.25 VDC or higher on terminals [+] and [-] on the flame safeguard amplifier? | If not: pilot pressure too low. Increase pilot pressure. |
| Commercial pilot: 1.0 micro amps or higher on terminals FC + and -? | If not: pilot pressure too low. Increase pilot pressure. |
| Alarm light blinking on the flame safeguard (FSG)? | Record the flash code from the alarm light, investigate its cause, then push the reset button. |
Burner airflow matters too. The start-up section says proper air velocity over the burner is critical, and that a unit outside specification may have sporadic shutdowns. The pressure drop across the burner should be 0.625 to 0.675 in. wg for natural gas, or 0.8 to 0.9 in. wg for LP.
How do you check a flame failure step by step?
- Record the code. If the flame safeguard alarm light is blinking, write down the flash code and look into its cause before you press reset, as the chart directs.
- Prove the supply fan and burner airflow. Connect a manometer to the burner differential sensing probes. Correct the reading to 0.625 to 0.675 in. wg (natural gas) or 0.8 to 0.9 in. wg (LP) with fan speed or the burner baffles.
- Read the flame signal on pilot only. Per 694984, with the main valve closed the signal should read above 1.25 VDC at the burner control test ports on Honeywell systems. On Baso systems, measure with the pilot lit and no main gas; the minimum is 1 µA DC.
- Check pilot gas pressure. The quick start guide sets pilot gas pressure at 1.5 to 3 in. wg. The chart says a low signal means pilot pressure is too low. The Honeywell start-up section also notes that in some cases reducing pilot gas pressure can increase flame signal, so adjust within the range while you watch the meter.
- Lock out and pull the flame rod. Clean a dirty or corroded rod with emery cloth. Replace the rod if the rod or its porcelain is cracked or deteriorated.
- Inspect the flame rod wire and connections. Our practical advice: a chafed lead or a loose terminal reads like a weak flame, so check it while the rod is out.
- Re-check the signal with the main burner lit. It should stay above 1.25 VDC and steady (694984).
- Only then look at the control. If the rod, wiring, pilot pressure and burner airflow all check out and the signal is still low, have the burner control and its flame amplifier tested against the control maker's instructions before you replace them.
Greenheck's seasonal maintenance list in 482886 says to inspect and clean the flame rod or UV scanner, and that occasional replacement of the flame rod and spark rod may be necessary for best performance. If the rod is original and the porcelain is crazed, it is a wear item.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Flame rod | Senses the flame; clean it, or replace it if the rod or porcelain is cracked (482886) | Greenheck 452942 Flame Rod, Direct Fired Burner |
| Flame rod wire | Lead from the flame rod to the burner control; match the old wire | Greenheck 851211 Flame Rod Wire |
| Pilot assembly | Listed as a pilot with spark and flame rod; match H1343 on your pilot | Greenheck 453900 Pilot with Spark & Flame Rod, H1343 |
| Flame amplifier | Plug-in flame amplifier listing; match the model on your burner control | Greenheck 383928 Flame Amplifier, R7847A1082 |
| Flame safeguard | Burner control listing; replace only after the rod, pilot and airflow check out | Greenheck 386999 Control, Flame Safeguard, RM7897A2002/U |
Which units this applies to
- Greenheck DGX direct gas-fired make-up air units covered by document 482886.
- Greenheck TSU and VSU industrial space heat units covered by the same manual.
- Older direct-fired units built before the current manual have their own IOM. Use the manual that matches your unit's nameplate.
Scope: Flame signal values, chart checks and burner pressure values are from Greenheck document 482886 (Models DGX, TSU and VSU) and the Pilot Ignition Quick Start Guide 694984. The amplifier and burner control listings are not stated in those documents for any one unit. Match the model printed on your control before ordering one, and confirm by serial number.
Before you order
Read the unit model and serial number from the nameplate, the burner control model from its label, and the part number off the old flame rod or pilot assembly if it is readable. Note whether the unit burns natural gas or LP. To confirm fit, contact us or email help@totalhvacparts.com with the model, serial number and old part number.
Frequently Asked Questions
What flame signal does a Greenheck direct-fired make-up air unit need?
Greenheck manual 482886 says the signal on a Honeywell burner control must be above 1.25 VDC and steady. Baso controls need at least 1 µA DC, measured with the pilot lit and no main gas flowing.
How do you clean a flame rod on a Greenheck direct-fired burner?
Greenheck's troubleshooting chart says to clean a dirty or corroded flame rod and remove corrosion with emery cloth. If the rod or its porcelain is cracked or deteriorated, replace it.
Why does a low flame signal point to pilot gas pressure?
The chart in 482886 lists 'Pilot pressure too low. Increase pilot pressure.' when the signal is under 1.25 VDC (Honeywell) or under 1.0 micro amps (commercial pilot). The quick start guide sets pilot gas pressure at 1.5 to 3 in. wg.
Should I reset the flame safeguard before troubleshooting?
Record the flash code from the alarm light first and investigate its cause, then push the reset button. That is the order Greenheck's chart gives.
Can burner airflow cause flame failure on a direct-fired unit?
Yes. Greenheck says proper air velocity over the burner is critical and that a unit outside specification may have sporadic shutdowns. Set the burner pressure drop to 0.625 to 0.675 in. wg for natural gas.
Sources
- Greenheck document 482886, Direct Gas and Industrial Space Heat Make-Up Air, Installation, Operation and Maintenance Manual (Models DGX, TSU, VSU), Rev. 12, December 2025
- Greenheck document 694984, Pilot Ignition Quick Start Guide, direct gas make-up air, Rev. 6, April 2018
- Live product titles for the parts listed above, as shown on each product page
Direct gas-fired make-up air units carry line voltage, high-voltage ignition and natural gas or LP. Service should be performed only by qualified personnel, following Greenheck's manual for your unit, local gas codes and your facility's lockout/tagout procedures.