If a Greenheck direct gas-fired make-up air unit never lights its pilot, Greenheck manual 482886 has you prove gas and airflow first, then ask one question: is a spark visible or audible during the trial for ignition? If not, the chart lists crossed spark and flame wires, an incorrect spark plug gap (set it to 0.062 in.), a defective spark plug or a faulty spark generator. The spark rod (Greenheck 452943) and the spark generator are the usual parts.
In what order does Greenheck troubleshoot a pilot that won't light?
The 120V industrial pilot chart in document 482886 (Direct Gas and Industrial Space Heat Make-Up Air IOM, Rev. 12) asks these questions in this order:
| Step | Question in the chart | If the answer is no |
|---|---|---|
| 1 | Inlet gas pressure between the minimum and maximum values shown on the direct gas label? | Correct the inlet gas pressure. |
| 2 | Pressure drop across the burner 0.625 to 0.675 in. wg for natural gas (0.8 to 0.9 in. wg for LP)? | Adjust fan speed and/or burner baffles. |
| 3 | Air in the gas line? | Purge the gas line. |
| 4 | Pilot gas valve passing pressure to the pilot test port? | Pilot gas valve (PV) faulty. Replace pilot gas valve. |
| 5 | Pilot gas pressure set correctly? | Set pilot gas pressure to recommended value. |
| 6 | Is a spark visible or audible during the trial for ignition? | See the spark causes below. |
| 7 | Flame light on the flame safeguard (FSG) illuminated? | Continue with the flame signal checks. |
The commercial pilot charts start with the supply fan and control power: is the fan operating correctly, and is there 24 VAC between terminals W1 and C? They then ask whether the pilot flame is visible through the sight glass before moving to gas pressure and spark.
What causes no spark on a Greenheck direct-fired burner?
When there is no visible or audible spark during the trial for ignition, the 482886 chart lists four causes:
| Cause (482886) | What to do |
|---|---|
| Spark and flame wires crossed | Uncross the wires and reconnect them (trace both leads from the burner to the control). |
| Incorrect spark plug gap | Set spark plug gap to 0.062 in. |
| Defective spark plug | Replace the spark rod. |
| Faulty spark generator | Replace the spark generator. |
The chart uses the term spark plug. The maintenance section of the same manual calls it the spark rod and says occasional replacement of the flame rod and spark rod may be necessary for best performance.
How do you check it step by step?
- Confirm the call for heat and the fan. On commercial pilot units, check for 24 VAC between W1 and C, and confirm the supply fan runs.
- Check inlet gas pressure against the minimum and maximum on the direct gas label, which 482886 places on the outside of the unit on the control center side.
- Check burner airflow with a manometer on the burner differential sensing probes: 0.625 to 0.675 in. wg natural gas, 0.8 to 0.9 in. wg LP.
- Purge air from the gas line on a new install or after gas work.
- Put a gauge on the pilot test port. No pressure with the pilot valve energized points to the pilot gas valve. Greenheck's quick start guide 694984 sets pilot gas pressure at 1.5 to 3 in. wg.
- Watch and listen for spark during the trial for ignition. Do not hold the spark lead by hand.
- Lock out and inspect the spark rod. Check the porcelain, the electrode and the gap. Set the gap to 0.062 in.
- Inspect the spark wire and its connector. Confirm the spark and flame leads are not crossed. Replace a cracked boot or a wire with burned insulation.
- If the rod, gap and wire are good and there is still no spark, the chart points to the spark generator.
Once the pilot lights, measure the flame signal. Greenheck calls for above 1.25 VDC and steady on Honeywell systems. Our article on direct-fired flame failure and flame rod checks covers that step.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Spark rod | Makes the ignition spark; gap 0.062 in. per the 482886 chart | Greenheck 452943 Spark Rod, Direct Fired Furnace |
| Spark generator | High-voltage source for the spark; a faulty generator is a listed cause of no spark | Greenheck 450496 Spark Generator, Honeywell, Q624A1014/B |
| Spark wire | High-voltage lead to the spark rod; check for crossed spark and flame wires | Greenheck 460507 Spark Wire, Wha40A-609D |
| Rajah connector | Terminal on the spark wire; replace if cracked or loose | Greenheck 452944 Rajah Connector, Spark Wire |
| Pilot gas valve | 'Pilot gas valve (PV) faulty. Replace pilot gas valve.' (482886) | Greenheck 464540 Pilot Gas Valve, Cv100P5N |
| Pilot assembly | Listed as a pilot with spark and flame rod; match H1343 on your pilot | Greenheck 453900 Pilot with Spark & Flame Rod, H1343 |
Which units this applies to
- Greenheck DGX direct gas-fired make-up air units covered by document 482886.
- Greenheck TSU and VSU industrial space heat units covered by the same manual.
- Older direct-fired units built before the current manual have their own IOM. Use the manual that matches your unit's nameplate.
Scope: The chart order, spark causes, 0.062 in. gap and burner pressure values are from Greenheck document 482886 (Models DGX, TSU and VSU). The pilot gas pressure range is from Greenheck quick start guide 694984. The spark generator, wire and pilot listings are not tied to a specific unit in those documents, so match the old part's number before ordering.
Before you order
Read the unit model and serial number from the nameplate and the part number or model printed on the old spark generator, pilot valve or pilot assembly. To confirm fit, contact us or email help@totalhvacparts.com with the model, serial number and old part number.
Frequently Asked Questions
What spark gap does a Greenheck direct-fired burner use?
Greenheck manual 482886 says: set spark plug gap to 0.062 in. An incorrect gap is one of four causes it lists for no spark.
Why is there no spark on my Greenheck make-up air unit?
The 482886 chart lists crossed spark and flame wires, an incorrect spark plug gap, a defective spark plug or a faulty spark generator.
What pilot gas pressure does Greenheck specify?
Greenheck's Pilot Ignition Quick Start Guide (694984) sets pilot gas pressure at 1.5 to 3 in. wg.
How do I know the pilot gas valve is bad?
The chart asks whether the pilot gas valve is passing pressure to the pilot test port. If not, it says: pilot gas valve (PV) faulty, replace pilot gas valve.
Sources
- Greenheck document 482886, Direct Gas and Industrial Space Heat Make-Up Air, Installation, Operation and Maintenance Manual (Models DGX, TSU, VSU), Rev. 12, December 2025
- Greenheck document 694984, Pilot Ignition Quick Start Guide, direct gas make-up air, Rev. 6, April 2018
- Live product titles for the parts listed above, as shown on each product page
Direct gas-fired make-up air units carry line voltage, high-voltage ignition and natural gas or LP. Service should be performed only by qualified personnel, following Greenheck's manual for your unit, local gas codes and your facility's lockout/tagout procedures.