Skip to content

WaterFurnace 5 Series E13, E14, E72 or E73 Sensor Error: Which Thermistor to Replace

On a WaterFurnace 5 Series 500A11 R-454B unit, E13 is a non-critical AXB sensor alert, E14 is a critical AXB sensor lockout, and E72 or E73 means the suction temperature or leaving air temperature (LAT) sensor reading is invalid. WaterFurnace's O&M manual OMW5-0016W gives "faulty wiring or a defective sensor" as the possible causes for E72 and E73. The likely parts are the LAT thermistor 12P555-06 — WaterFurnace Leaving Air Temperature Thermistor 5-Series and the suction line thermistor for your unit size.

What do E13, E14, E72 and E73 mean?

From the fault table and descriptions in OMW5-0016W (pp.34-36):

Code Table description Lockout Reset What the unit does
E13 Any Other Sensor Err. No Auto Alert. Fault is recognized when a sensor faults that is not critical to heat pump operation.
E14 Sensor Err for EEV or HW. Yes Hard or Soft Lockout. Fault is recognized when a sensor faults that is critical to heat pump operation.
E72 Suction Temperature Sensor is invalid (-76 to 392 F). No Auto Safe mode: "The EEV will be positioned at 50%."
E73 Leaving Air Temperature Sensor is invalid (-76 to 392 F). No Auto Normal operation continues with an Error 73 display on the thermostat.

The manual says the E14 sensors "would include the HW Temperature limit sensor" and the E13 sensors "would include the performance, energy monitoring and refrigeration sensors." The 7 Series manual IM2700ANA (p.37) has the same four rows for its Aurora AXB.

Which sensor goes with which code?

The 5 Series R-454B service parts list (OMW5-0016W p.97) names each AXB thermistor. The suction line part changes with unit size:

Sensor Part number (OMW5-0016W p.97) Related code (our reading)
Leaving air (LAT) 12P555-06, all sizes 018–072 E73
Suction line 12P555-09 (018); 12P555-10 (030, 042); 12P555-05 (024, 036, 048, 060, 072) E72
Liquid line heating 12P555-03, all sizes E13 (refrigeration sensor)
Entering water 12P560-01, all sizes E13 (performance sensor)
Leaving water 12P560-02, all sizes E13 (performance sensor)
Hot water limit (HWG) 12P505-10, all sizes E14 (HW sensor)

Our reading: the manual does not map each sensor to a code. E72 and E73 name their sensors directly. The E13 and E14 entries above follow the groups the manual describes ("performance, energy monitoring and refrigeration sensors" for E13; "Sensor Err for EEV or HW" for E14), so a sensor used by the EEV could also show as E14. The AID Tool shows the actual sensor readings, so use it to find the one that is out of range.

How do you find the bad sensor?

  1. Read the code and the sensors in the AID Tool. OMW5-0016W says the AID Tool lets you see "sensor inputs, system outputs, timer, etc." along with fault history. Look for a reading that is blank, pinned or far from the real temperature.
  2. Note what the unit is doing. With E72 the EEV sits at 50%. With E73 the unit keeps running and the thermostat shows Error 73. E14 locks the unit out.
  3. Isolate power. Apply lockout/tagout before opening the control box.
  4. Check the wiring first. Both E72 and E73 list faulty wiring as a cause. Trace the sensor lead to the AXB, reseat the plug and look for cut or pinched wires.
  5. Measure the thermistor. Unplug it and compare its resistance at a known temperature with the thermistor table on p.46 of OMW5-0016W.
  6. Replace the sensor that fails. Use the part number for your unit size from the table above.
  7. Clear and verify. E13, E72 and E73 reset automatically once the reading is valid. The manual says the E73 display "will be removed when the problem has been resolved." E14 needs a hard or soft reset: see how to reset a WaterFurnace lockout.

What should the thermistors read?

Rows from the "Compressor & Thermistor Resistance" chart in OMW5-0016W (p.46), "Microprocessor Resistance (Ohms)":

Temperature (°F) Resistance (ohms)
32 33809–31487
50 20570–19230
68 12889–12093
77 10310–9688
95 6723–6337

The chart does not say which sensors it covers. The 7 Series manual uses two charts (IM2700ANA p.50): 10k for FP1, FP2, HWL, LWT and LLT, and 1k for the discharge line, suction line, LAT, compressor ambient and EWT sensors. If a 5 Series reading is far from every row, check the sensor type for your model before you condemn it.

Parts that fix it

Component Role Link
Leaving air temperature thermistor Primary fix for E73 when the LAT sensor is open, shorted or out of range. OMW5-0016W p.97: 12P555-06, all sizes. 12P555-06 — WaterFurnace Leaving Air Temperature Thermistor 5-Series
Suction line thermistor (size 018) E72 fix on the 018 size. Other sizes use 12P555-10 or 12P555-05. 12P555-09 — WaterFurnace Suction Temperature Thermistor 5-Series 012-018
Liquid line heating thermistor Refrigeration sensor on the AXB. OMW5-0016W p.97: 12P555-03, all sizes. Our title says 7-Series; the 7 Series manual uses the same number. 12P555-03 — WaterFurnace Liquid Line Heating Temperature Thermistor 7-Series
Entering water thermistor Performance sensor (E13). OMW5-0016W p.97: 12P560-01, all sizes. 12P560-01 — WaterFurnace Entering Water Thermistor 50" (Used In Harness)

For the hot water limit sensor on a 7 Series, see our 7 Series hot water generator article.

Which units this applies to

  • WaterFurnace 5 Series 500A11, R-454B, sizes 018–072, per OMW5-0016W.
  • The E13/E14/E72/E73 rows also appear in the 7 Series 700A11 manual IM2700ANA, but its sensor part numbers differ (for example, LAT and suction line are 12P556-01 there).

Scope: Part numbers in this article are from the OMW5-0016W parts list. Older 5 Series units, R-410A builds and other WaterFurnace lines have their own lists. Match the number on the old sensor or your unit's manual.

Before you order

Have the model number, serial number and the code shown in the AID Tool. Note the unit size, because the suction line thermistor changes by size. Browse the WaterFurnace replacement parts collection, or contact us at help@totalhvacparts.com and we will confirm the right sensor.

Frequently Asked Questions

Does E73 stop a WaterFurnace heat pump?

No. OMW5-0016W says normal operation continues with an Error 73 display on the thermostat. It is not a lockout and resets automatically.

What happens on E72?

The suction temperature reading is invalid, and the manual says the EEV will be positioned at 50%. Check the wiring and the suction line sensor.

Is E14 a lockout?

Yes. E14 is a critical AXB sensor error for EEV or hot water sensors, with a hard or soft reset. E13 is only an alert.

Which suction thermistor fits my 5 Series?

OMW5-0016W lists 12P555-09 for size 018, 12P555-10 for 030 and 042, and 12P555-05 for 024, 036, 048, 060 and 072.

Sources

WaterFurnace heat pumps involve line voltage, 24 VAC control circuits and pressurized refrigerant. Service should be done only by qualified personnel, following the unit manual and your site's lockout/tagout procedure.

← WaterFurnace E4 Freeze Detection FP2 or E...BAC Cooling Tower Uneven Spray or Dry Fil... →