On an LG Multi V 5, CH34 means the outdoor unit shut down on high pressure and CH35 means it shut down on low pressure. The LG MULTI V 5 Outdoor Unit Service Manual (Error No. 34, p.156 and Error No. 35, p.157) lists a defective pressure sensor among the causes, but its flowcharts check service valves, charge, fans and airflow first and only point to the sensor when it disagrees with a manifold gauge. In that case the sensors LG lists for ARUM Multi V 5 units are LG EBD64386504 Pressure Sensor – Multi V outdoor unit (high) and LG EBD64386505 Pressure Sensor – Multi V outdoor unit (low); a failed outdoor fan motor is the other common part.
What are the CH34 and CH35 trip points?
| Error | Display | Trip condition in the manual |
|---|---|---|
| 34, compressor high pressure safety | 341 / 342 / 343 | One compressor's high pressure above 4,000 kPa (580 psi) for 10 seconds. The system shuts off after an excessive pressure increase that occurred ten (10) consecutive times. |
| 35, low side pressure | 351 / 352 / 353 | Sum of all compressor inverter frequencies below 30 Hz and low side below 110 kPa (15.95 psi) for 1 minute; or in cooling, low side below 400 kPa (58.02 psi) for 1 minute with high side below 2,200 kPa (319.08 psi); or in heating, low side below 230 kPa (33.36 psi) for 1 minute with high side below 1,800 kPa (261.07 psi). Shuts off after three consecutive occurrences. |
The last digit is the unit: 1 for the master, 2 for slave 1, 3 for slave 2.
What causes CH34?
The manual lists a defective high pressure sensor, defective indoor or outdoor fans, refrigerant overcharge, damaged piping, defective indoor or outdoor EEVs, a blocked outdoor unit in cooling or a blocked indoor filter in heating, a clogged service valve, a defective outdoor unit PCB, a defective indoor unit pipe temperature sensor and a defective hot gas valve.
How do I troubleshoot CH34?
- Confirm the service valves are open.
- Check the communication cable and piping connections and repair any fault.
- Check the refrigerant amount; add or remove refrigerant as needed.
- Check the fans: the indoor fan in heating, the outdoor fan in cooling. The manual's action is to replace fan components and refers to Error Nos. 105 to 107.
- Look for blockage: the indoor filter in heating, the outdoor heat exchanger in cooling. Clean as needed.
- Compare the high pressure sensor value with the manifold gauge. If they differ, replace the high pressure sensor. If they match, check the indoor unit EEV, the indoor unit PCB and the installation.
What causes CH35, and how do I troubleshoot it?
For Error No. 35 the manual lists a defective low pressure sensor, defective indoor or outdoor fans, damaged refrigerant piping, a blocked outdoor coil in heating or a blocked indoor filter in cooling, a clogged service valve, a defective outdoor unit PCB and a defective indoor unit pipe temperature sensor. The flowchart checks (the page layout makes the exact branch order hard to read, so use this as a checklist):
- Confirm the service valves are open.
- Check the communication cable, piping and installation.
- Check the refrigerant amount.
- Check the fans: the outdoor fan in heating, the indoor fan in cooling.
- Check the strainer. The manual notes that a large temperature difference across the strainer, enough to show frost or ice, points to a clog.
- Compare the low pressure sensor with the manifold gauge. If they differ, replace the low pressure sensor. If they match, check the indoor and outdoor EEVs, the indoor unit PCB and the installation.
- Check for leaks or damaged piping, repair, and recharge.
Sensor, fan or system: how do I decide?
The gauge comparison is the deciding test in both flowcharts. If the sensor and the gauge agree, the pressure is real and a new sensor will not clear the code; the fault is in airflow, charge, an EEV or a valve. If they disagree, the sensor is the part to change. For the sensor's own voltage checks, see the Error No. 42/43 checks on p.161 of the same manual.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| High pressure sensor (16500HP) | Replace for CH34 when it disagrees with the manifold gauge. | LG EBD64386504 Pressure Sensor – Multi V outdoor unit |
| Low pressure sensor (16500LP) | Replace for CH35 when it disagrees with the manifold gauge. | LG EBD64386505 Pressure Sensor – Multi V outdoor unit |
| Outdoor fan motor, ARUM096-241BTE5 | Defective outdoor fan is a listed cause of both codes. | LG EAU43080032 DC Fan Motor, Outdoor – Multi V outdoor unit |
| Outdoor fan motor, ARUM072BTE5 | The fan motor LG lists for ARUM072BTE5. | LG EAU43080022 DC Fan Motor, Outdoor – Multi V outdoor unit |
| Outdoor EEV coil and body (location 661400 / 552200) | Defective EEVs are listed causes; LG lists the coil and body separately. LG notes that MJX63992003 is a newer design that fits only units built after LG's change and is not a substitute for MJX62751401, so check the serial number. |
LG EAP65270715 Expansion Valve Coil – Multi V outdoor unit LG MJX63992003 Expansion Valve Body – Multi V system |
460V DTE5 units use different fan motors from the BTE5 units; check the fit list on the product page or your model page.
Which units this applies to
- LG Multi V 5 outdoor units ARUM072 through ARUM241, BTE5 (208-230V) and DTE5 (460V).
- The pressure sensors also appear in LG's fit lists for many Multi V IV, Multi V III and Multi V i models, but the trip values above are from the Multi V 5 manual only.
Scope: Trip values, causes and check order are from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 34 (p.156) and Error No. 35 (p.157). Part numbers, locations and fits come from LG's parts-by-model data as shown on our ARUM096BTE5 model page and product pages.
Before you order
Read the full model and serial number from the outdoor unit nameplate (and the indoor unit nameplate for indoor faults), note the exact error number shown, including the unit digit, and, if you can, the LG part number on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.
Frequently Asked Questions
At what pressure does an LG Multi V 5 trip CH34?
The manual's Error No. 34 trips when one compressor's high pressure is above 4,000 kPa (580 psi) for 10 seconds, and the system shuts off after ten consecutive occurrences.
Why does my LG Multi V show CH35 in heating?
In heating, the manual's limit is low side below 230 kPa (33.36 psi) for 1 minute with high side below 1,800 kPa. Listed causes include low charge or leaks, a blocked outdoor coil, fans, a clogged strainer or service valve, EEVs and the low pressure sensor.
Should I replace the pressure sensor for CH34?
Only if it disagrees with a manifold gauge. The flowchart checks valves, charge, fans and airflow first, then replaces the high pressure sensor if its value differs from the gauge.
What is the difference between CH24 and CH34?
CH24 is the high pressure switch opening. CH34 is the high pressure safety based on the pressure sensor value.
Sources
- LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error No. 34 (p.156), Error No. 35 (p.157) and Error Code Tables (p.129); cited by name and page; LG publishes no printed form number for this manual; read page by page, not linked
- LG parts-by-model data for Multi V 5 ARUM models as shown on our LG model pages (for example ARUM096BTE5) and each product page's fit list
LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.