Greenheck Direct-Fired MUA Locked Out on a Gas Pressure Switch: Reset, Test, Replace

On a Greenheck direct gas-fired make-up air unit with the optional gas pressure switches, a burner that is locked out with the fan running is often a tripped high or low gas pressure switch (PS3 and PS4). Greenheck manual 482886 says both switches shut down and lock out the burner, both need a manual reset, and they are typically set at 8 in. wg (high) and 3 in. wg (low). Correct the gas pressure first. Replace the switch (for example Greenheck 386641 or 386640) only if it will not hold at correct pressure.

What do the gas pressure switches do on a Greenheck direct-fired unit?

Greenheck document 482886 (Direct Gas and Industrial Space Heat Make-Up Air IOM, Rev. 12) describes them in the accessory identification and start-up sections:

Item What 482886 says
High gas pressure switch Will automatically shut down and lock out burner operation if the manifold gas pressure is too high
Low gas pressure switch Will automatically shut down and lock out burner operation if the inlet gas pressure is too low
Reset Both gas pressure switches will require a manual reset
Reset location The manual reset is a push button located on the top of the pressure switches
Typical settings High typically 8 in. wg (2 kPa); low typically 3 in. wg
Labels in the troubleshooting chart PS3 and PS4, marked optional

Because these switches are optional, not every unit has them. Look on the gas train before you go further.

What does the troubleshooting chart say?

The direct gas-fired heat pages of 482886 list a tripped switch as a cause when the burner will not light:

Chart item (482886) Corrective action
(Optional) high/low gas pressure switch(es) (PS3 and PS4) tripped Correct gas pressure and reset.
Inlet gas pressure between the minimum and maximum values shown on the direct gas label? If not, correct the inlet gas pressure.
Inlet gas pressure too high Reduce inlet gas pressure to below the maximum gas pressure.
Inlet gas pressure too low to provide high fire Increase inlet gas pressure to above the minimum input for maximum output value.

A switch that trips again right after reset is telling you something about the gas supply. Fix the pressure, not the switch, unless the readings prove the switch wrong.

How do you check it step by step?

  1. Find which switch tripped. Look at both switches on the gas train. Note which one needs a reset before you press anything.
  2. Read the direct gas label. 482886 places it on the outside of the unit on the control center side. It gives the minimum and maximum inlet gas pressure for your unit.
  3. Put a gauge on the inlet. Read static pressure, then read again with the burner firing at high fire. A low switch that trips only at high fire points to a supply that sags under load.
  4. Compare to the switch settings. Greenheck gives typical settings of 8 in. wg (high) and 3 in. wg (low). Your switch may be set differently; read its dial.
  5. Correct the gas pressure to fall within the label's range, then press the reset button on top of the switch.
  6. Test the switch if it will not reset (general practice, not a 482886 step). With power locked out and the gas pressure confirmed inside the range, check the switch contacts with a meter. A switch that stays open with correct pressure on it, or that will not latch after reset, is the part to replace.
  7. Restart and watch a full cycle, from light-off through high fire, with the gauge still on.

Our practical advice: when you replace a switch, set the new one to the same value as the old one and record it on the unit. The value on the old switch dial is the starting point, not a guess.

Parts that fix it

Component Role Link
Low gas pressure switch Locks out the burner if inlet gas pressure is too low; manual reset Greenheck 386641 Low Pressure Gas Switch, Honeywell, C6097A3012
High gas pressure switch Locks out the burner if manifold gas pressure is too high; manual reset Greenheck 386640 High Pressure Gas Switch, Honeywell C6097B3028
Low gas pressure switch, Antunes Alternate brand listing; match the switch on your gas train Greenheck 387326 Low Pressure Gas Switch, Antunes, 8103116202
High gas pressure switch, Antunes Alternate brand listing; match the switch on your gas train Greenheck 387325 High Pressure Gas Switch, Antunes, 8101111202

Which units this applies to

  • Greenheck DGX direct gas-fired make-up air units covered by document 482886.
  • Greenheck TSU and VSU industrial space heat units covered by the same manual.
  • Older direct-fired units built before the current manual have their own IOM. Use the manual that matches your unit's nameplate.

Scope: Switch functions, typical settings, reset location and chart entries are from Greenheck document 482886 (Models DGX, TSU and VSU). The switches are optional on these units. The 482886 accessory table names Honeywell C6097B1028 (high) and C6097A1012 (low); the Honeywell listings here are C6097B3028 and C6097A3012, and the Antunes listings are not named in the manual. Match the brand, full model and range printed on your old switch.

Before you order

Read the unit model and serial number from the nameplate and the full model and range off the old switch. Note whether it is the high or the low switch, and the gas type. To confirm fit, contact us or email help@totalhvacparts.com with the model, serial number and old part number.

Frequently Asked Questions

How do you reset a gas pressure switch on a Greenheck make-up air unit?

Greenheck manual 482886 says both gas pressure switches need a manual reset, and the reset is a push button on the top of the switch. Correct the gas pressure first.

What are the typical gas pressure switch settings on a Greenheck direct-fired unit?

482886 gives typical settings of 8 in. wg (2 kPa) for the high gas pressure switch and 3 in. wg for the low gas pressure switch.

Why does my low gas pressure switch keep tripping?

Greenheck manual 482886 says the low switch locks out the burner when inlet gas pressure is too low. Check the inlet pressure against the direct gas label at high fire, correct it, then reset.

Do all Greenheck direct-fired units have gas pressure switches?

No. The 482886 troubleshooting chart marks the high and low gas pressure switches (PS3 and PS4) as optional.

Sources

Direct gas-fired make-up air units carry line voltage, high-voltage ignition and natural gas or LP. Service should be performed only by qualified personnel, following Greenheck's manual for your unit, local gas codes and your facility's lockout/tagout procedures.