LG Multi V Heat Recovery Unit CH201, CH202 or CH203: Sensor Error and Which Thermistor Set to Order

On an LG Multi V heat recovery system, CH201, CH202 and CH203 are sensor faults at a heat recovery (HR) unit: the liquid pipe sensor, the subcooling inlet sensor and the subcooling outlet sensor. The LG MULTI V 5 Outdoor Unit Service Manual (Error Nos. 201C, 202C, 203C, p.202) lists a bad connection, an open or shorted sensor, or a PCB fault. On PRHR**3A units LG lists all three sensors as one assembly, LG EBG61107342 NTC Thermistor Assembly – Multi V system, whose item spec reads "SC_OUT, SC_IN, Liquid".

What do CH201, CH202 and CH203 mean?

Code LG description (MV5 p.202)
201 Heat recovery unit liquid piping temperature sensor error
202 Heat recovery unit subcooling inlet piping temperature sensor error
203 Heat recovery unit subcooling discharge piping temperature sensor error

The detail line is the same for all three: "Abnormal sensor value (sensor has disconnected or has shorted out)." LG shows these with a C and the HR unit number; the MV5 page maps "C01" to "C16" to HR units 1 to 16, so the code tells you which HR unit to open. The subcooling sensors work with the HR unit's subcooling EEV (SCEEV), which LG describes as "Controls Subcooling" (MV5 p.88).

What resistance should the HR unit sensors read?

The LG Multi V S service manual MFL69740704 prints the values on its 201C-203C page: "10 ℃[50 ℉] = 10 kΩ : 25 ℃[77 ℉] = 5 kΩ : 50 ℃[122 ℉] = 1.8 kΩ". That matches LG's item spec for the PRHR**2A-series set, EBG61107309: three "5KOHM,5%,PIPE THERMISTOR" sensors.

How do I check a CH201, CH202 or CH203?

LG gives three steps rather than a flowchart (MV5 p.202; LG MULTI V S Outdoor Unit Service Manual Error Nos. 201-203; LG manual MFL69740704):

  1. Connections. "Check the connections of the temperature sensor and the lead cable."
  2. Sensor value. "Is value of temperature sensor normal? If not replace sensor" (MFL69740704). Measure each of the three sensors against the table above at the actual pipe temperature.
  3. Board. "If the sensor connection and values are correct, replace the outdoor unit PCB."

Step 3 and the cause list both say "outdoor unit PCB" in all three LG manuals we checked, even though the sensors sit in the HR unit. We quote it as printed. If the sensor and its lead test good and the code stays, call LG technical support to confirm which board to change before ordering one.

Field practice, not from the manual: the three sensors run as one harness on LG's assemblies, so compare all three readings. One reading far from the other two at the same pipe temperature points to that sensor; all three wrong together points to the plug or the lead.

Which thermistor assembly fits my HR unit?

HR unit models (LG fit list) Assembly LG item spec
PRHR023A, 033A, 043A, 063A, 083A; PRHR023C, 024C, 033C, 034C, 043C, 044C LG EBG61107342 NTC Thermistor Assembly – Multi V system "HR unit PRHR033.ENCXLEU SC_OUT, SC_IN, Liquid"
PRHR020, 030, 040; PRHR020A, 021A, 022A, 030A, 031A, 032A, 040A, 041A, 042A LG EBG61107309 NTC Thermistor Assembly – Multi V heat recovery unit Three "5KOHM,5%,PIPE THERMISTOR" sensors

LG lists EBG61107342 at location 263230 on the PRHR033A and PRHR083A, and EBG61107309 on the PRHR032A. Because LG lists the three sensors as one assembly, our reading is that a single failed sensor is replaced as the whole assembly.

Parts that fix it

Component Role Link
HR unit thermistor assembly (liquid, SC in, SC out), PRHR**3A and C series Replace when any of the three sensors reads open, short or out of tolerance. LG EBG61107342 NTC Thermistor Assembly – Multi V system
HR unit thermistor assembly (three 5 kΩ pipe sensors), PRHR**0, 0A, 1A, 2A As above, for the older HR models. LG EBG61107309 NTC Thermistor Assembly – Multi V heat recovery unit

Which units this applies to

  • LG Multi V heat recovery units in the PRHR series listed above, on Multi V 5 and Multi V S heat recovery systems.
  • Codes 201, 202 and 203 with the C suffix and HR number (C01 to C16).

Scope: Code meanings and steps are from the MV5 manual p.202, the MV S manual and LG manual MFL69740704; resistance values are from MFL69740704. Fits, locations and item specs are LG's parts-by-model data as shown on our pages. Other HR or mode-selector models may list a different sensor.

Before you order

Read the full model and serial number from the unit's nameplate, note the exact code shown (including any unit or HR-number digits), and if you can, the LG part number printed on the part you are replacing. Note which HR unit number the code shows. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, code and the readings you took.

Frequently Asked Questions

What is CH202 on an LG Multi V?

A heat recovery unit subcooling inlet piping temperature sensor error: the sensor reads disconnected or shorted. The C number after the code identifies the HR unit.

What resistance should an LG HR unit sensor have?

LG's Multi V S manual MFL69740704 lists 10 kΩ at 10 °C (50 °F), 5 kΩ at 25 °C (77 °F) and 1.8 kΩ at 50 °C (122 °F).

Which sensor set fits a PRHR033A?

LG lists EBG61107342, whose item spec names the SC_OUT, SC_IN and liquid sensors, at location 263230 on the PRHR033A.

Does LG say to replace a board for CH201 to CH203?

Only after the sensor connection and values test correct. LG's step reads "replace the outdoor unit PCB"; confirm the board with LG technical support before ordering.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual (no printed form number), Heat Recovery Unit Parts Functions p.88; Error Code Tables p.135; Error Nos. 201C, 202C, 203C p.202. Cited by name and page; not linked.
  • LG MULTI V S Outdoor Unit Service Manual, Error Nos. 201, 202, 203.
  • LG Multi V S service manual MFL69740704, 201C#HR to 203C#HR page (values).
  • LG parts-by-model and item-spec data as shown on our LG model pages (PRHR032A, PRHR033A, PRHR083A) and product pages.

Heat recovery units carry line voltage and connect to refrigerant piping under pressure. Service should be performed only by qualified personnel, following LG's service manual for your system and your facility's lockout/tagout procedures.