LG Multi V CH104 or CH105: Outdoor Unit and Fan PCB Communication Errors — Wire or Board?

On an LG Multi V 5, CH104 is a communication error between the master and slave outdoor units, and CH105 means the fan PCB did not receive a signal from the inverter compressor PCB. The LG MULTI V 5 Outdoor Unit Service Manual (Error No. 104, p.182 and Error No. 105, p.185) puts wiring, DIP switches, grounding and supply voltage ahead of any board. If those check out, the manual's final action for CH104 is to replace the outdoor main PCB, which LG lists as LG EBR79669907 Main PCB Assembly – Multi V 5 outdoor unit for every ARUM Multi V 5 size, with LG EBR79669909 Main PCB Assembly – Multi V outdoor unit as LG's recommended one-way substitute.

What do CH104 and CH105 mean?

Error Display Meaning in the manual
104 1041 / 1042 / 1043 Communication error between master and slave outdoor units. The master shows the number of the unit that stopped transmitting; a slave shows its own number.
105 1051 / 1052 / 1053 Fan PCB did not receive a signal from the inverter compressor PCB.

These are communication faults inside the outdoor unit or between outdoor units. Indoor-to-outdoor communication is CH05 and CH53, covered in LG CH05 and CH53 communication error.

How do I troubleshoot CH104?

The manual lists two causes: power wiring or communication cable loose, disconnected or shorted, and a defective outdoor unit main PCB. The flowchart checks:

  1. Communication cable. Is the outdoor-to-outdoor cable installed correctly? If not, connect it.
  2. Slave DIP switches. Are the slave outdoor unit DIP switches set correctly? If not, change them.
  3. Main PCB power. Is the main PCB powered? If not, connect the power wiring.
  4. Noise. Press reset; a communication error may have been temporary. If noise is the cause, use shielded communication wire.
  5. Ground. Is the GND wire connected to the chassis? If not, connect it.
  6. Polarity. Are A and B connected properly? Do not swap communication line A with B.
  7. Board. If all of the above pass, replace the main PCB.

How do I troubleshoot CH105?

Error No. 105 causes: the inverter compressor PCB and fan PCB connection is not correct, the fan PCB is not powered, the inverter compressor PCB and/or fan PCB is defective, or the power supply to the inverter 1 and inverter 2 terminals on the main PCB is below 13.5 V DC. The checks:

  1. Fan PCB LED. Is the fan PCB communication LED (yellow) blinking normally? If not, check the communication cable between the inverter compressor PCB and the fan PCB.
  2. Inverter PCB LED. Is the inverter compressor PCB communication LED (yellow) blinking normally? If not, check the same cable.
  3. Supply. Is the power to the inverter 1 and/or inverter 2 terminals on the main PCB below 13.5 V DC? If so, check the power supply to those terminals.
  4. Fan PCB. Check the fan PCB assembly.
  5. Inverter PCB. If the fault remains, the manual's final step is to replace the inverter PCB assembly.

Parts that fix it

Component Role Link
Outdoor main PCB (all ARUM Multi V 5) CH104 final action; also the source of the 13.5 V DC inverter 1 / 2 supply checked for CH105. LG EBR79669907 Main PCB Assembly – Multi V 5 outdoor unit
Outdoor main PCB, LG substitute LG lists EBR79669909 as a one-way substitute for EBR79669907 (from LG's substitution data; the EBR79669909 product page's own fit list is shorter). LG EBR79669909 Main PCB Assembly – Multi V outdoor unit
Fan PCB, ARUM096-241BTE5 CH105: fan PCB not receiving or defective. LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit
Inverter PCB, ARUM096/121/192/216/241BTE5 CH105 final action. LG EBR88279008 Inverter PCB Assembly – Multi V 5 outdoor unit

Fan and inverter boards differ by size and voltage: LG lists EBR88279204 as the fan PCB for ARUM096 to ARUM241 DTE5 and EBR88279003 as the inverter PCB for ARUM096, 121, 192, 216 and 241 DTE5; the 072 size uses its own fan boards, and the 072, 144 and 168 sizes use different inverter boards. Match your model's fit list.

Which units this applies to

  • LG Multi V 5 outdoor units ARUM072 through ARUM241, BTE5 and DTE5. CH104 applies to combinations of two or three outdoor units (master plus slaves).

Scope: Codes, causes and checks are from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 104 (p.182) and Error No. 105 (p.185). Board fits and the substitute relationship come from LG's parts data on our product pages and model pages such as ARUM096BTE5.

Before you order

Read the full model and serial number from the outdoor unit nameplate (and the indoor unit nameplate for indoor faults), note the exact error number shown, including the unit digit, and, if you can, the LG part number on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.

Frequently Asked Questions

What does 1042 mean on an LG Multi V 5?

Error No. 104 shown on slave 1. Per the manual, a slave unit displays its own error number, while the master displays the number of the outdoor unit that has not been transmitting.

Can swapped A and B wires cause CH104?

Yes. The flowchart checks that A and B are connected properly and says not to swap communication line A with B.

What voltage should the inverter terminals on the main PCB have?

The manual's CH105 and CH106 checks treat power to the inverter 1 and inverter 2 terminals below 13.5 V DC as a fault.

Should I buy EBR79669907 or EBR79669909?

LG lists EBR79669909 as a one-way substitute for EBR79669907 and recommends the substitute. Do not put EBR79669907 in place of an EBR79669909.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error No. 104 (p.182), Error No. 105 (p.185); cited by name and page; LG publishes no printed form number for this manual; read page by page, not linked
  • LG parts-by-model data for Multi V 5 ARUM models as shown on our LG model pages (for example ARUM096BTE5) and each product page's fit list

LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.