LG Multi V CH04 Drain Overflow: Float Switch, Drain Pump or Indoor PCB?

CH04 on an LG Multi V indoor unit is a drain overflow error: condensate has lifted the float far enough to open the float switch circuit. The LG MULTI V 5 Outdoor Unit Service Manual (Error No. 04, pp.138-139) lists three causes: a drain pump or float switch fault, a badly located or clogged drain pipe, or the indoor unit PCB. Check the water level, the pump and the float switch resistance before ordering. On 1-way cassettes such as the ARNU073TUD4, LG lists the switch assembly LG 6601A20013S Switch Assembly – Multi V VRF Indoor Unit and the pump LG AHA75113321 Condensate Pump Assembly – Multi V indoor unit.

What trips CH04?

The MV5 page notes: "* If the float rises higher than half its height, then the circuit opens and the unit automatically stops." The float switch plugs into CN-FLOAT and the pump into CN-DPUMP on the indoor PCB (LG MULTI V S Outdoor Unit Service Manual, Error No. 04); the LG Multi V ducted indoor unit service manual MFL69041302 labels them CN_FLOAT(BL) and CN_D_PUMP(WH), and words the M1/M2/M3 ducted fault simply as "Malfunction of drain pump".

How do I check a CH04?

The MV5 flowchart asks these questions; the order below is ours, from the drain pan outwards:

  1. Water level. "Is the drain pan filled half-way with water? (Float is halfway up to the float switch.)"
  2. Pump running. "Is the drain pump operating? (Sound / drain noise / contact / etc.)"
  3. Pump blocked. "Is the drain pump clogged?" If so: "Remove any debris and clean the pump."
  4. Pump supply. "For the indoor unit PCB, does the voltage have the correct output?" LG manual MFL69740704 gives 220 V at the indoor PCB drain pump connector; check your unit's wiring diagram for its pump.
  5. Float switch. "Is the float switch resistance short when measured?" MFL69740704 gives the reading: low position "short 0 ohm", high position "Open".
  6. Drain line. "Check the height and slope of the drain head." The MV5 page gives the slope as "1/50~1/100".

The actions printed on the chart are: "Replace the drain pump.", "Replace the float switch.", "Replace the indoor unit PCB or reconnect the connector." and "Replace the indoor unit PCB." The text copies we read do not show which arrow leads where. Our reading: a pump with correct voltage that does not run is the pump; a float switch that does not read short with the float down is the switch; correct readings on both with the code still set points to the connector or the indoor PCB.

Field practice, not from the manual: clear the trap and the vent on the drain line and pour water into the pan with power on. If the pump runs and the level drops, the fault is downstream, not in the unit.

Which drain parts fit my indoor unit?

LG lists drain parts by chassis. On the ARNU073TUD4, the pump sits at location 158591 and a "Switch Assembly" at location 266010. LG's description does not say "float"; our reading is that 6601A20013S is the float switch assembly, as it is the only switch in that unit's list. Its LG fit list is the ARNU073, 093 and 123 TUD4, ARNU183 and 243 TSA4 and TTD4, and ZRNU183 and 243 TSAA. Other chassis use other pumps:

Chassis (LG fit list) Condensate pump
ARNU073/093/123 TUD4, ARNU183/243 TTD4, ARNU073TUC4 LG AHA75113321 Condensate Pump Assembly – Multi V indoor unit
ARNU M1A4, M2A4, M3A4 ducted (e.g. ARNU123M2A4) LG 5859A20002D Condensate Pump Assembly – Multi V indoor unit
4-way cassettes TNA4, TNC2/4, TMA4, TMC2/4, TPC2/4 LG AHA32883202 Condensate Pump Assembly – Multi V indoor unit

LG has several pump changes on the 1-way cassettes with numbers it rates as not interchangeable, so check the number on the old pump. Full chassis list: LG Multi V condensate pumps by chassis.

Parts that fix it

Component Role Link
Switch assembly (float switch), TUD4/TSA4/TTD4 Replace when the switch does not read short with the float down. LG 6601A20013S Switch Assembly – Multi V VRF Indoor Unit
Condensate pump, TUD4/TTD4 Replace when it has correct voltage but does not run, or stays blocked after cleaning. LG AHA75113321 Condensate Pump Assembly – Multi V indoor unit
Condensate pump, M1A4/M2A4/M3A4 ducted Same test, ducted chassis. LG 5859A20002D Condensate Pump Assembly – Multi V indoor unit
Condensate pump, 4-way cassettes Same test, TN/TM/TP chassis. LG AHA32883202 Condensate Pump Assembly – Multi V indoor unit

Which units this applies to

  • LG Multi V indoor units with a drain pump and float switch that display CH04, on Multi V 5, Multi V S and other Multi V systems using the same indoor code table.
  • Part fits as listed above from LG's parts-by-model data.

Scope: Causes, flowchart questions and the float note are from the MV5 manual Error No. 04 (pp.138-139); float switch readings and the 220 V figure are from LG manual MFL69740704; connector names are from the MV S manual and LG manual MFL69041302. The float-switch identification of 6601A20013S is our reading.

Before you order

Read the full model and serial number from the unit's nameplate, note the exact code shown (including any unit or HR-number digits), and if you can, the LG part number printed on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, code and the readings you took.

Frequently Asked Questions

What does CH04 mean on an LG Multi V indoor unit?

A drain overflow error. LG lists a drain pump or float switch fault, a badly located or clogged drain pipe, or the indoor unit PCB.

What should an LG float switch read?

LG manual MFL69740704 says the switch reads short (0 ohm) in the low position and open in the high position.

When does an LG indoor unit stop on high water?

LG says that if the float rises higher than half its height, the circuit opens and the unit stops automatically.

Which drain pump fits an ARNU123M2A4?

LG lists 5859A20002D on the ARNU123M2A4 and the other M1A4, M2A4 and M3A4 ducted sizes.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual (no printed form number), Error No. 04, pp.138-139. Cited by name and page; not linked.
  • LG Multi V S service manual MFL69740704, Error 04 pages (float switch readings, pump voltage).
  • LG MULTI V S Outdoor Unit Service Manual, Error No. 04 (CN-DPUMP, CN-FLOAT).
  • LG Multi V ducted indoor unit service manual MFL69041302, self-diagnosis table and wiring diagram.
  • LG parts-by-model data as shown on our LG model pages and product pages.

Indoor unit service involves line-voltage wiring, rotating fans and condensate near live parts. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.

← LG Multi V CH237 or CH238: Indoor-to-Outd...WaterFurnace E4 Freeze Detection FP2 or E... →