Greenheck Vari-Green Fan Runs but Motorized Damper Stays Shut: Transformer 385253 Damper Contact Checks

On a Greenheck Vari-Green fan with the factory-mounted transformer, a motorized backdraft damper can be switched by that transformer. Greenheck's Vari-Green manual (document 473681) says transformer PN 385253 "has the ability to signal a motorized back draft damper to open/close as the motor starts/stops." It has a N.O./N.C. auxiliary contact that changes state at a control voltage of 1.85 VDC. Our reading: if the fan runs and the damper stays shut, check that contact, the damper's power source and the motor pack, in that order.

How does the transformer open the damper?

The 473681 manual describes two jobs for the factory transformer:

  • 24 VDC for the motor and a remote device. "A factory mounted transformer is available to supply 24 VDC power to the motor when the 0-10V signal is by others." The manual says the transformer can power a remote device drawing up to 400 mA at 24 VDC.
  • An auxiliary contact for the damper. "A N.O./N.C. set of contacts is provided which will change state when above or below a control voltage of 1.85 VDC." The wiring diagram labels this "Trip Point = 1.85VDC" and rates the contact 10A @ 24-240VAC and 5A @ 30VDC.

The page 10 diagram, "Motorized damper operation with Vari-Green® Control", labels the transformer's N.C., N.O. and COM contact terminals, a "Neutral Line (Damper Power Source)" and the "Auxiliary Contact". Our reading of the diagram: the damper is fed from its own power source through the auxiliary contact, so the contact switches the damper's power; it does not supply it. The manual says only "See wiring diagram for example."

The trip point lines up with the motor. The same manual says that on a 0-10 VDC signal, "From 0-1.9V, the motor will be off, and will operate in the 2-10V range." Our reading: as the speed signal rises past 1.85 VDC, the contact changes state at about the point the motor starts running.

Why does the fan run with the damper shut?

  1. Is the damper powered at all? Our reading of the diagram: the damper's supply comes from its own source through the auxiliary contact. Field practice, not from the manual: check the breaker or fuse feeding that circuit, and measure for voltage at the transformer's COM terminal.
  2. Is the right contact used? The manual does not say which contact the damper uses. Our reading: a damper that should open with the fan is wired through the contact that closes above 1.85 VDC. Field practice, not from the manual: if the damper is open when the fan is off and shut when it runs, it is on the wrong contact (N.C. instead of N.O.).
  3. Is the contact switching? Field practice, not from the manual: with the fan commanded above 2 V, measure across the contact in use. If the signal is above the trip point and the contact never changes state, the transformer is the suspect.
  4. Is the load within the rating? The contact is rated 10A @ 24-240VAC and 5A @ 30VDC.
  5. Is something else wired to the 24V terminal? The manual warns: "Do not connect an external 24V supply to the transformer's control terminal labeled 24V."
  6. Does the motor pack itself work? If voltage reaches the damper actuator and it still will not open, move on to the damper. For WD-100 dampers, the MP-100A manual (463548) lists a racked damper, screws interfering with the blades or linkage, excessive spring tension, voltage drop and building negative pressure. Our article on WD-100 dampers that won't open covers those checks.

Parts that fix it

Component Role Link
Factory-mounted transformer PN 385253 in 473681: 24 VDC supply plus the N.O./N.C. damper contact with a 1.85 VDC trip point Greenheck 385253 Vari-Green Control Transformer, 85V-277V
WD-100 motor pack, 115-230V Replacement spring-return actuator kit for WD-100 dampers on 110-120V or 208-240V Greenheck 826840 Internal Actuator Kit, Multi Products, MP-100 Act, 115-230V, 50/60HZ
WD-100 motor pack, 24V Replacement actuator kit for 24V damper circuits Greenheck 826848 Internal Actuator Kit, Multi Products, MP-100 Act, 24V, 60HZ
End switch kit Proves the damper fully open, for systems that hold the fan until the damper opens (Greenheck 452723) Greenheck 851038 Limit Switch, G, Wd, Vcd

For a fan that will not run at all, see Vari-Green motor not running. Other Vari-Green and damper parts are in Valent, Innovent & Greenheck Replacement Parts.

Which units this applies to

  • Greenheck fans with Vari-Green motors and the factory-mounted transformer PN 385253 (473681)
  • Motorized backdraft dampers switched by the transformer's auxiliary contact, for example WD-100 dampers with MP-100A motor packs (463548). 473681 does not name a damper model.

Scope: The transformer functions, trip point, ratings and warnings come from Greenheck document 473681, Vari-Green Motor and Controls Installation, Operation and Maintenance Manual, Rev. 14, August 2019. The damper troubleshooting comes from Greenheck document 463548, MP-100A Motor Pack (electric actuators with spring return for WD-100 series dampers), Rev. 9, April 2025. The manual shows the damper wiring only as a diagram, so follow the wiring diagram for your fan and damper. Match the damper motor pack voltage to its label.

Before you order: Note the fan model and serial number, the Vari-Green motor part number, the transformer label and the damper motor pack model and voltage. If the nameplate is missing, see how to find Greenheck parts by serial number or without a nameplate. To confirm a part, contact us or email help@totalhvacparts.com.

Frequently Asked Questions

How does a Greenheck Vari-Green fan open a motorized damper?

Greenheck manual 473681 says the factory transformer, PN 385253, can signal a motorized backdraft damper to open/close as the motor starts/stops, using a N.O./N.C. set of contacts that changes state at a control voltage of 1.85 VDC.

What is the trip point of the Vari-Green transformer damper contact?

1.85 VDC. The wiring diagram labels it "Trip Point = 1.85VDC". A 0-10 VDC Vari-Green motor is off from 0 to 1.9 V and runs from 2 to 10 V.

What is the rating of the Vari-Green transformer auxiliary contact?

10A at 24-240 VAC and 5A at 30 VDC, per Greenheck manual 473681.

Can I power other devices from the Vari-Green transformer?

The manual says it can power a remote device drawing up to 400 mA at 24 VDC. It also warns not to connect an external 24V supply to the transformer's terminal labelled 24V.