{"product_id":"lg-zrum036gss0","title":"LG ZRUM036GSS0 Multi V S (R32) 36,000 BTU Heat Recovery \/ Heat Pump Outdoor Unit","description":"\u003cp\u003e\u003cstrong\u003eLG ZRUM036GSS0\u003c\/strong\u003e is a 36,000 Btu\/h (3 ton) \u003cstrong\u003eMulti V S (R32)\u003c\/strong\u003e variable refrigerant flow outdoor unit, configurable for heat recovery or heat pump operation, running on R32 at 208-230V, 3-phase power. It replaces \u003cstrong\u003eARUM036GSS5\u003c\/strong\u003e.\u003c\/p\u003e\n\u003cp\u003eFrom the LG submittal: 31 A MCA and 40 A MOP.\u003c\/p\u003e\n\u003ch3\u003eSystem design and installation\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eIndoor units: any LG Multi V S (R32) indoor units at matching voltage. Total connected indoor capacity can run to roughly 120% of this unit's rated capacity — confirm against the combination data manual under Documentation.\u003c\/li\u003e\n\u003cli\u003eHeat recovery: pair with PRHR branch-distribution units for simultaneous heating and cooling.\u003c\/li\u003e\n\u003cli\u003eElectrical: 208-230V, 3-phase, 31 A MCA \/ 40 A MOP; disconnect and breaker field supplied.\u003c\/li\u003e\n\u003cli\u003eRefrigerant: R32 — charged on site per the piping design in the engineering manual.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eLG VRF equipment must be designed and commissioned by an LG-trained contractor; the VRF limited warranty document is linked under Documentation.\u003c\/p\u003e","brand":"LG","offers":[{"title":"Default Title","offer_id":48587883020509,"sku":"ZRUM036GSS0","price":8044.6,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0835\/2127\/4077\/files\/Multi-V-S-U7-U60A-Front.png?v=1789569336","url":"https:\/\/totalhvacparts.com\/products\/lg-zrum036gss0","provider":"TotalHVACParts","version":"1.0","type":"link"}